Wuhan HeZhong Electric Equipment Manufacture Co.,Ltd

Wuhan Hezhong Electric Equipment Manufacture Co., Ltd ELECTRICAL TECHNOLOGY SECURITY EXPERTS

Manufacturer from China
Active Member
8 Years
Home / Products / Electrical Test Equipment /

DC System Electrical Test Equipment High Precision Grounding Fault Detection Use

Contact Now
Wuhan HeZhong Electric Equipment Manufacture Co.,Ltd
City:wuhan
Province/State:hubei
Country/Region:china
Contact Now

DC System Electrical Test Equipment High Precision Grounding Fault Detection Use

Ask Latest Price
Video Channel
Brand Name :United electrical
Model Number :HZJD-612
Certification :ISO9001, ISO14001, OHSAS18001
Place of Origin :Wuhan, China
MOQ :1 pcs
Price :negotiable
Delivery Time :7 working days
Packaging Details :1 pcs / wooden box with wrapping film
Output Signal Frequency :2.5Hz
Signal No-load Output Voltage :±20V±5%
Signal Voltage Amplitude Error :<5%
Signal Short Circuit Output Current :≤80mA
Output Port Anti-impact Ability :400V DC impact
Signal Current Detection Sensitivity :0.5mA
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

DC System Grounding Fault Tester Electrical Test Equipment

Product Description:

HZJD-612 DC grounding fault tester is suitable for any voltage level DC system, equipped with high precision detection clamp meter, greatly improve the detection range and anti interference ability via the efficient processing of many kinds of signals.

Product Features:

◆ Easy to operate, turn on the power switch can be used directly.

◆ More applicable voltage level, DC system 220V,110V,48V,24V.

◆ Wide applicable range, apply to any type of electric plant, substation, coal mine, chemical plant ect..

◆ Portable, signal receiver comes with batteries, does not need external power, convenient to carry with.

◆ Find the grounding point with DC system power on, do not effect the system working.

◆ Strong anti-interference ability, overcome the effect of system distributed capacitance.

Product Parameters:

Signal Generator Output Signal Frequency 2.5Hz Signal Receiver Signal Current Detection Sensitivity 0.5mA
Signal No-load Output Voltage ±20V±5% Signal Generator Impedance 40kΩ
Signal Voltage Amplitude Error <5% Max Output Current 2.5mA
Signal Short Circuit Output Current ≤80mA Receiver Display number 0~19
Output Port Anti-impact Ability 400V DC impact Dimension 210x100x32mm²
Power Voltage AC 220V±10% A Jaw Size Ø50mm
Voltage Frequency 50Hz±5% B Jaw Size Ø7mm x 9mm
Input Insurance 200mA Complete Machine Max Ground Resistance 300kΩ
Maximum Power 3W Measurement Accuracy 0~4.5kΩ, error≤0.5kΩ
Dimension 300x270x200mm³ 4.5kΩ~300kΩ, error≤10%

Quality Guarantee: One year quality guarantee after shipment.