Add to Cart
Anti-interference Inter-frequency Dielectric Loss Transformer Testing Equipment
Product Description:
HZGS-206 auto anti-interference dielectric loss tester is a high precision instrument which the power plant and substation use to automatically measure the dielectric loss tangent values and capacitance.
Product Features:
◆ Use converter technology to ensure the accurate measurement under strong electric field interference.
◆ With positive and negative connecting ways measure ground or non-ground high voltage electrical equipment. Also can measure the capacitance voltage transformer tgδ and the main capacitor C1,C2 capacitance.
◆ Equipped with high voltage boosting transformer, and voltage zero-crossing switch off, lightning protection ect.
◆ Can take measurement for CVT transformer.
Product Parameters:
High voltage Output | 0.5~10kV for each gear increase 500V, total 10 gears, capacitance: 1500VA |
Accuracy | tg δ: ±(read*1.0%+0.04%) Cx: ±(read*1.0%+5PF) |
Resolution | tg δ: 0.01%; Cx: 1pF |
Measurement Range |
0.1%<tg δ<50% 3PF<Cx<60000PF when 10kV, Cx≤30000PF when 5kV, Cx≤60000PF |
Power Source | AC220V±10%, 50/60±1Hz |
Working Condition | -15℃~50℃, relative humidity: <80% |
Quality Guarantee: One year quality guarantee after shipment.